GGS low-voltage drawer switchgear is widely used in power distribution centers of power plants, substations, industrial enterprises, and high-rise buildings, as well as in motor control centers (MCC). It serves as a low-voltage complete distribution device for centralized control of power distribution and motor operation in AC systems operating at 50-60Hz, with rated voltages up to 660V and rated currents up to 4000A. It is also used for reactive power compensation.

model:

  • Commodity name: Low voltage cabinet GGS

Phone:

  • Product Description
  • Product overview

    GGS low-voltage drawer switchgear is widely used in power distribution centers of power plants, substations, industrial enterprises, and high-rise buildings, as well as in motor control centers (MCC). It serves as a low-voltage complete distribution device for centralized control of power distribution and motor operation in AC systems operating at 50-60Hz, with rated voltages up to 660V and rated currents up to 4000A. It is also used for reactive power compensation.

     

    Main technical parameters

    Rated insulation voltage: AC 660V, AC 1000V

    Rated working voltage: AC 380V, AC 660V

    Rated frequency: 50Hz

    Rated current of horizontal busbar: 1250~4000A

    Rated current of vertical busbar: 1000A

    Maximum current of power supply circuit: 2500A

    Maximum current of drawer circuit: 500A

    Maximum capacity of control motor: 320KW

    Peak withstand current of horizontal busbar (0.1S): 63KA, 105KA, 176KA

    Horizontal bus short time withstand current (1S): 30 KA, 50 KA, 80 KA, 100 KA Vertical bus peak withstand current (0.1S): 63 KA, 105 KA

    Vertical bus short time withstand current (15): 30 KA, 50 KA rated power frequency withstand voltage (1min): 2500V

    Secondary power frequency withstand voltage (1min): 2500V

    Protection class: IP30, IP40

    External dimensions width * depth * height mm: 600 (800,1000) *800 (1000) *2200

     

    Product use environment

    1. The ambient air temperature shall not be higher than +40℃ and lower than-5℃, and the average temperature within 24h shall not be higher than +35℃. If it exceeds the limit, the operation shall be reduced according to the actual situation;

    2. Indoor use: the altitude of the place where it is used shall not exceed 2000m;

    3. When the relative temperature of the surrounding air is +40℃, it should not exceed 50%. At a lower temperature, a larger relative temperature is allowed, such as +20℃, which should be 90%. The influence of condensation may occur occasionally due to the change of temperature should be taken into account;

    4. The slope of the device installation to the vertical plane shall not exceed 5℃, and the whole cabinet column shall be relatively flat (in line with GBJ232-82 standard);

    5. The device shall be installed in a place without violent vibration and impact, and not enough to cause undue corrosion of electrical components;

    6. If the user has special requirements, it can be negotiated with the manufacturer.

Keywords:

The Low voltage cabinet

Related Products


Low voltage cabinet GGD2

GGD type AC low voltage distribution cabinet is suitable for power plants, substations, factories and other power users of AC 50HZ, rated working voltage 380V, rated working current up to 3150A distribution system, as power, lighting and distribution equipment energy conversion, distribution and control.