Submit Message

High voltage cabinet HXGN □-12

The HXGN□-12 Box-type AC Metal-Enclosed Ring Main Switchgear is a new generation of high-voltage electrical products designed and developed by our factory, incorporating advanced foreign technologies and tailored to China's power supply requirements. It is suitable for urban grid renovation and construction needs.

model:

  • Commodity name: High voltage cabinet HXGN □-12

Phone:

  • Product Description
  • Overview

    The HXGN□-12 Box-type AC Metal-Enclosed Ring Main Switchgear is a new generation of high-voltage electrical products designed and developed by our factory, incorporating advanced foreign technologies and tailored to China's power supply requirements. It is suitable for urban grid renovation and construction needs. The performance meets the standards of IEC298 "AC Metal-Enclosed Switchgear and Control Equipment" and GB3906 "3~35kV AC Metal-Enclosed Switchgear." It is applicable to three-phase AC systems in factories, schools, residential areas, and high-rise buildings with system voltages of 3~10kV and rated frequencies of 50Hz, used for receiving and distributing electrical energy. It can be used for ring main power supply and terminal power supply.

     

    Product based on standards

    GB38043~63kV AC high voltage load switch
    GB39063~35kV AC metal closed switchgear
    GB11022General technical conditions for high voltage switchgear
    GB9969.1General instructions for use
    DL404Technical conditions for ordering indoor AC high voltage switchgear
    IEC420A combination of high voltage AC load switch and fuse

    Conditions of use

    1, ambient temperature: maximum temperature +40℃; minimum temperature-15℃;

    2. Relative humidity: the daily average value is not greater than 95%; the monthly average value is not greater than 90%

    3. Altitude: not higher than 1000m

    4. The intensity of the earthquake should not exceed 8 degrees

    5, saturated steam pressure: the daily average value is not greater than 2.2x10-3Mpa; the monthly average value is not greater than 1.8x10-3Mpa

    6. Places without fire, explosion danger, serious pollution, chemical corrosion and violent vibration.

    7. Special use conditions (areas beyond the normal use environment mentioned above) should be negotiated with the manufacturer when ordering

     

    Technical parameters

    Order numberRated voltageUnitDistribution conforms to switch and combination electrical-ISARC1Distribution conforms to switch and combination electrical-ISARC2
    1rated voltagekV1212
    2rated frequencyHz5050
    3Rated current of main busA630630
    4Rated short time withstand currentkA/s20/2-
    5Rated peak withstand currentkA50-
    6Rated short circuit closing currentkA50-
    7Rated active load breaking currentA630-
    8Rated closed loop breaking currentA630-
    9No-load transformerkVA-1600
    10Rated cable charging currentA1010
    11Rated short circuit breaking currentkV-31.5
    12Rated switching transfer currentA-3150
    13Power frequency withstand voltage (1min)kVAlternately, relatively: 42, between isolation breaks: 48-
    14Lightning impulse withstand voltagekVAlternately, relatively: 75, between isolation breaks: 85 (peak)-

     

    Order instructions

    1. Product name, model, primary line scheme and quantity

    2. Name, model and specification and quantity of electrical equipment installed in the vacuum ring network cabinet

    3. Arrangement diagram, plan layout diagram and secondary schematic diagram of vacuum ring network cabinet

    4. The material specifications of the main busbar and branch busbar can be proposed by the customer, or supplied according to the manufacturer's standard if there is no requirement

    5. Special requirements for cabinet color shall be negotiated with the manufacturer (if no requirements are required, the manufacturer's standard shall be supplied)

Keywords:

High voltage cabinet

Related Products


High voltage cabinet XGN2-12

The XGN2-12 box-type fixed metal-enclosed switchgear is a high-voltage switchgear system developed and researched by Xi'an Electrical Research Institute. The primary components used in the equipment have all been redesigned, offering higher insulation levels and protection ratings compared to the currently widely used drawer-type switchgear and GG-1 (A) F type switchgear.

High voltage cabinet XGN66-12

High voltage cabinet XGN66-121.SummaryThe XGN66-12 (GGX2-10) molded high-voltage vacuum switchgear is a new product jointly designed and developed by the Ministry of Mechanical Industry and the Ministry of Electric Power Industry to replace the GG-1A type high-voltage switchgear. This switchgear complies with IEC298 international standards and GB3906-91 national standards, and features reliable "five-proof locking functions." It can be equipped with vacuum circuit breakers of models ZN21, VS¹, ZN66, ZN28, or other types, offering strong compatibility, an elegant appearance, and easy maintenance, making it a superior distribution device.Note: According to the "High Voltage Switchgear Model Compilation Method" and GB/T2900.20-94 "Electrical Terminology for High voltage switchgear", the original product model "GG×2-10" is changed to XGN66-12", the technical parameters and performance of the two are exactly the same.2. Features of new products● Use vacuum circuit breaker as the main switch, less maintenance, no pollution, high life.● reinforced insulation.The air electrical gap is greater than or equal to 125mm, the creepage distance of porcelain insulators is greater than or equal to 210mm, and the creepage distance of resin insulators is greater than or equal to 230mm. The short-term condensation on the insulation surface does not affect its insulation level.● The live body is enclosed in the metal shell, and the main busbar between cabinets is supported by insulating bushings and used as inter-cabinet shielding.● Safe and reliable operation, easy maintenance.3. Basic skeleton sizeRated currentHigh (m m)Width (m m)Deep (m m)Below 1250A275010001200Below 3150A2750120012004. Purpose and scope of useThis product is suitable for three-phase AC power grid with rated voltage 3~10KV and frequency 50Hz. It is a complete set of distribution equipment for receiving and distributing electric energy and controlling, monitoring and protecting circuits.Environmental conditions used:a. Indoor air temperature +40℃~-15℃;b. The altitude does not exceed 1000m;c. The daily average air humidity (relative humidity) is not greater than 95%, and the monthly average is not greater than 90%;d. There is no flammable, explosive and chemical corrosive gas, no serious pollution, no violent vibration.5. Technical dataorder numberParameter nameonePositionparameter values1rated voltageKV36102maximum voltageKV3.67.2123rated frequencyHz504specifiedinsulationhorizontal1 minute power frequency withstand voltageRelative, identicalKV243242Between the breaksKV263648Full wave impact pressure resistanceRelative, interstitialKV406075Between the breaksKV4366855rated currentA630 1250 2500 31506Rated breaking currentKA20 31.5 407Rated operating cycleMinus 0.3S plus minus 180S plus minus8Rated dynamic stability current (peak)KA50 80 1009Rated thermal stability currentKA20 31.5 4010Rated thermal stability timeS4

High voltage cabinet KYN28-12

This switchgear is a complete set of switchgear for three-phase AC 50Hz/60Hz single bus and segmented single bus systems. It is suitable for substations and distribution rooms in power plants, power systems, oil, chemical industries, enterprises, and institutions, serving to distribute electrical energy. It can control and protect power equipment such as generators, transformers, motors, and reactive power compensation devices.

High voltage cabinet ZBW-12

The ZBW series modular substations (European style) and the ZBW (N) series modular substations combine high-voltage electrical equipment, transformers, low-voltage electrical equipment, and more into a compact integrated distribution device commonly known as European-style containerized substations. They are used in urban high-rise buildings, rural and urban structures, residential areas, high-tech development zones, small and medium-sized factories, mines, oil fields, and temporary construction sites for power reception and distribution in the electrical system.
< 1 >